Normal temperature filter deaerator

Gategory:

Key words:Water Filter、UV Sterilizer、Ion Exchange Water softener

Removing oxygen dissolved in water is of great significance to prevent corrosion of boilers or other water-using equipment and ensure their safe and economical operation. For many years, people have been troubled by the fact that the traditional deaeration method cannot achieve the ideal deaeration effect due to the harsh external conditions, or cannot operate economically.
Inquiry

Product introduction and principle

Deoxidation of iron scraps in the deoxidation method has the characteristics of simple equipment, simple operation, small capital investment and low operating cost. As long as the shortcomings such as unstable deoxidation effect of iron scraps and the need for regular activation are overcome, it is actually an industrial boiler. an ideal deoxidation method. Mechanism of filtration deoxidization at room temperature: The sponge iron particles produced by patented technology are mainly composed of iron. Its loose and porous internal structure provides a surface area 5-10 times that of ordinary iron filings, which can make the oxygen and iron in the water rapidly increase. A thorough oxidation reaction occurs to stabilize the dissolved oxygen in the water below 0.05mg/L. The reaction formula is:

2Fe+2H2O+O2→2Fe(OH)2

2Fe(OH)2+H2O+1/2O2→2Fe(OH)3

The reaction product can be washed with a certain intensity of backwash water (about 5 minutes). The consumption of sponge iron is very low. According to the difference in the amount of treated water and water quality, it is usually enough to replenish it once every 3-6 months. A small amount of iron ions (usually 0.2-0.5mg/L) has been added to the water after deoxygenation, which still meets the national water quality standards for hot water boilers. However, for steam boilers or feed water deaeration that has strict requirements for water Fe2+, iron removal can be installed after the existing deaerator to remove Fe2+ in the effluent of the deaerator to ensure the quality of boiler feed water. Normal temperature filter deaerator can be divided into automatic control and manual control.

22

 

Automatic control selection reference table

Model parameter name JMY–4 JMY–6 JMY–10 JMY–15 JMY–20 JMY–25 JMY–30 JMY–40 JMY–50
Water outlet (M3/h) 4 6 10 15 20 25 30 40 50
Off-device
Type Size
(mm)
diameter 400 500 600 700 800 900 1000 1100 1200
Tank height 2600 2600 2800 2800 2900 2900 3100 3100 3100
Footprint (side length) 500 600 900 1000 1200 1300 1400 1500 1600
Take over
Diameter(mm)
Import and Export 40 40 50 50 65 80 80 100 100
Backwash water 40 40 50 50 65 80 80 100 100
filler layer (mm) 1200 1200 1200 1200 1200 1200 1200 1200 1200
filler weight (Kg) 250 380 550 740 970 1250 1500 1850 2200
Equipment load (Kg) 660 910 1320 1800 2300 3100 3800 4600 5400
Working pressure (Mpa) 0.15–0.5MPa
Control mode Automatic control, timing backwash
Working temperature °C 8–50℃ (when >50℃, the user should ask the manufacturer in advance to deal with it)

 

JMY type normal temperature filter deaerator dimensions and installation drawing

11

Technical parameters

Water quality: softened water or demineralized water

Water inlet pressure: 0.2MPa-0.6MPa

Working temperature: 5℃-50℃

Filling height: 1200mm

Working flow rate: 20m/hr

Backwash intensity: 18L/m2·S

Each backwash time: 15-25 minutes

Automatic type is time or differential pressure control, automatic backwashing; manual type is differential pressure control, manual backwashing.

 

Technical Features

Deoxygenation can be achieved at room temperature, and the incoming water does not need to be heated;

The deoxidizing effect is stable and reliable, and the dissolved oxygen content in the effluent is stable ≤0.05mg/L, which meets the water quality standard of low-pressure boilers;

Complete variety of equipment, the control mode can be fully automatic or manual control mode according to user requirements;

There are no special requirements for installation, which overcomes the inconvenience that heat and vacuum deaeration must be installed at a high position;

The equipment can be arranged at a low position, occupying a small area, and the process is simple;

For the automatic deaerator, there is no need to install a backwash pump, and the system is simple.

 

Manual control selection reference table

Model parameter name YLY-4 YLY-6 YLY-10 YLY-15 YLY-20 YLY-25 YLY-30 YLY40 YLY-50
Water outlet (T/h) 4 6 10 15 20 25 30 40 50
Off-device
Shape size
(mm)
diameterФ 500 600 700 900 1000 1200 1300 1400 1600
height H 3000 3000 3150 3250 3250 3400 3400 3600 3600
occupancy 600 900 1000 1200 1400 1600 1700 1800 2000
Inlet and outlet pipe (mm) 32 40 50 50 65 80 80 100 100
Backwash pump water volume (T/H) 8 12 20 30 40 50 60 80 100
Packing layer height (mm) 1200 1200 1200 1200 1200 1200 1200 1200 1200
filler weight (kg) 400 550 750 1250 1500 2200 2500 3000 4000
Equipment load (kg) 900 1300 1800 3050 3700 5300 6500 7600 8800
Work stress 0.15-0.5Mpa
Control mode Manual control, differential pressure control backwash
Operating Temperature 8-50°C (when it is higher than 50°C, the user needs to propose in advance for the manufacturer to handle)

The above data is for reference only, and the data of each shipment shall prevail.